The working principle of the evaporative condenser is to send the high-temperature steam that needs to be condensed into the coil from the upper inlet of the heat exchange coil. The high-temperature steam releases heat in the heat exchange coil, and after being cooled, it undergoes a phase change and condenses into a liquid. Circulating spray water is used as the cooling medium outside the heat exchange coil. The spray water forms a uniform water film on the outer surface of the heat exchange coil. The water film absorbs the heat released by the hot steam in the coil and evaporates, and then passes through the fan. Carrying water vapor out of the evaporative condenser takes heat away from the coil.
When the temperature of the condensed steam medium is higher than 80°C, the spray water will easily form scale on the outer surface of the heat exchange coil, which will seriously affect the heat exchange effect and the service life of the equipment. In order to avoid this situation, our company has designed an evaporative condenser with a finned tube precooler. Into the condensing coil for evaporative condensation. Adding a pre-cooler can effectively alleviate the fouling problem. At the same time, because the pre-cooler adopts the air-cooled heat transfer method, which makes full use of the sensible heat transfer of the wind, the evaporative condenser is more water-saving and power-saving.
GHCooling is an experienced manufacturer of evaporative condensers.We can customize suitable evaporative condensers for customers according to o their site conditions. The products designed and manufacturered by GH Cooling have been recognized by the users. lf you are interested in our products, please contact us +86 18848963680.