A 40-foot container cooling tower drift eliminator (fill) are ready for shipment to Malaysian customer
The drift eliminator or cooling tower fill for Malaysian customer are ready for shipping. The drift eliminator are made of PVC
The drift eliminator should have the following basic characteristics:
- High water removal efficiency and low ventilation resistance. When the wind speed V =1m/s and the water density q=8m3/(m2·h), the interception efficiency η of the water separator should not be less than 75% (silica gel method), and the resistance should not be greater than 0.13 (Pa·m3) /N.
- It has sufficient assembly rigidity. Under normal operating conditions, its geometric shape should remain stable for a long time to ensure that the eliminator maintains a long-term stable high-efficiency and low-resistance operation effect.
- It has excellent properties of corrosion resistance, aging resistance and no deformation.
- The eliminator assembly block should have sufficient rigidity and strength. Under the condition of simple support, the test piece with a clear span of 1300mm under a uniform load of 300N/m 2 (38 ℃, 72h) shall have no obvious deformation at the support and loading surface, and the maximum deflection shall be ≤510mm.
- Simple structure, easy to process, economical and durable.